CTB-350
The Clean Burn Model CTB-350 waste oil boiler has an input rating of 350,000 BTU/hr and an output rating of 260,00 BTU/hr. The CTB-350 is UL listed for use in central heating systems.
With the mid-sized CTB-350, you spend 30 minutes cleaning every 1000 hours of operation. It is uniquely designed for installation flexibility. Engineered for use as a single boiler unit, or it can be used in combination with any Clean Burn boiler to create a system perfectly sized for any facility.
MODEL INFORMATION
FEATURES
		
	
	 Three-pass heat exchanger creates more heat efficiency
	
	
	Low-mass water design provides quick start -up
	
	
	Patented burner engineered exclusively for waste oil
	
	
	System is pre-wired, ready for installation
	
	
	Narrow cabinet designs provide installation flexibility
	
	
	Unequaled service and support from Clean Burn Distributors
	
	SPECS
		
| Model CTB-350 | Specs. | 
|---|---|
| BTU/hour input: | 350,000 (102 kW) | 
| BTU/hour output: | 260,000 (76.2 kW) | 
| Fuels | Used oils: Crankcase,ATF, hydraulic Fuel oils: #2, #4, and #5 fuel oil | 
| Heating Surface | 68 sq. ft. / 6.3 sqM | 
| Boiler water volume | 12 gal. / 45.4 L | 
| Design water flow per coil | 12 gal. / 45.4 L | 
| Cabinet dimensions | 56″ L x 34″ W x 34.5″ H 142cm x 86cm x 88cm | 
| Overall dimensions (with burner/breach/plumbing) | 74″ L x 39.25″ W x 41″ H 188cm x 100cm x 104cm | 
| Approx. Weight | 1240 lbs. / 562.4 kg | 
| Electrical Requirements | 115 VAC 60 Hz single phase* *230V/ 50Hz units also available | 
| Maximum oil consumption | 2.5 GPH / 9.5 lph | 
| Stack size | 8″ / 20cm | 
| Air compressor required | 2.5 CFM @ 25 PSI 4.25 m3/h @ 1.7 bar | 
| Recommended clean-out | 1000 hours | 
*Values indicated above are nominal. Actual values will vary depending on fuel and installation.